4.4 MP2000 Series Machine Controller Parameter Details

4.4.2 Motion Setting Parameter Details

4-44

( 14 ) Override

( 15 ) Position Reference Setting

OW

18

Override

Setting Range

Setting Unit

Default Value

0 to 32767

0.01%

10000

Description

Set the percentage of the Speed Reference Setting (OL

10) to output in units of 0.01%.

The override value is always enabled. Set to 10000 (fixed) when not using the override function.

Speed reference setting (OL

10)

× Override (OW

18) = Output speed

This parameter can be changed at any time to any value during execution of speed reference, and accelera-
tion/deceleration is performed immediately according to the set value.

When the override is set to 0, the output speed is 0 and the motor will not operate.

OL

1C

Position Reference Setting

Setting Range

Setting Unit

Default Value

-2

31

to 2

31

−1

Reference unit

0

Description

Set the position reference.

This parameter is used for the following motion commands.
1: POSING
2: EX_POSING
4: INTERPOLATE
6: LATCH

Position Mode (Positioning)
Latch Target Positioning (External positioning)
Interpolation
Interpolation Mode with Latch Input

Related Parameters
OW

09, bit 5: Position Reference Type

Position

Phase

Speed

Torque

50%

75%

100%

5000

7500

10000

10000

Override set value

Time

R

Position

Phase

Speed Torque