The modular system, 1×counter/16×digital input – Lenze EPM−T9XX Modular system User Manual

Page 108

Advertising
background image

1×counter/16×digital input

4

The modular system

4.23

L

4.23−2

EDSPM−TXXX−9.0−11/2009

1C/DI 16xDC24V

EPM – T430 1A

1

2

.0

3

.1

4

.2

5

.3

6

.4

7

.5

8

.6

9

.7

10

.0

11

.1

12

.2

13

.3

14

.4

15

.5

16

.6

17

.7

18

0

1

+

2

1

3

4

14

15

16

17

18

DC 24 V (DC 18 … 28.8 V)

.

A

B



‚

ƒ

epm−t128

epm−t131

Fig. 4.23−2

Front view and connection 1×counter/16×digital input

0

2 × status display .0 ... .7; LED
(green) is lit when a HIGH level is
recognised

1

Terminal strip assignment details

1

GND (reference potential)

2

Digital input E.0 or counter
input A

3

Digital input E.1 or counter
input B

4

Digital input E.2

...

...

16

Digital input E.14

17

Digital input E.15

18

GND (reference potential)

.

Connection to backplane bus

 Pre−assign the counter with a count

value

‚ Output the current count value
ƒ 32−bit counter with channel A and

channel B

Mode

Function

E.0

E.1

0

4−fold pulse evaluation

CLK

CLK

1

Pulse and direction evaluation

CLK

DIR

2

Clock up/clock down evaluation

CLK−UP

CLK−DOWN

3

Frequency measurement

CLK

4

Period measurement

CLK

No function

CLK

Clock signal of a connected encoder

HIGH level starts and / or stops the counting process

CLK−UP

Clock signal of a connected encoder

With each LOW−HIGH edge the counter counts up by 1

CLK−DOWN

Clock signal of a connected encoder

With each LOW−HIGH edge the counter counts down by 1

DIR

Indicates counting direction depending on signal level

LOW: Upcounter

HIGH: Downcounter

Status display and terminal
assignment

Counter mode overview

Advertising