Parameterising analog modules parameter data – Lenze EPM−T9XX Modular system User Manual

Page 303

Advertising
background image

Parameterising analog modules

Parameter data

12

Parameter setting via system bus (CAN) / CANopen

12.3

12.3.1

L

12.3−5

EDSPM−TXXX−9.0−11/2009

The following bytes with fixed assignment are available for parameter data:

Byte

Assignment

Lenze
setting

0

Activate / deactivate wire
breakage detection and
enabling/inhibiting diagnostic
alarm

1) 2)

Bit 0

Wire breakage detection for input E.0

00

h

0

Deactivated

^ 12.3−6

1

activated

Bit 1

Wire breakage detection for input E.1
0

Deactivated

^ 12.3−6

1

activated

Bits 2 ... 5

Reserved

Bit 6

0

Diagnostic alarm
inhibited

^ 12.3−6

1

Diagnostic alarm
enabled

1

reserved

Bits 0 ... 7

Reserved

2

Select signal function for
input E.0

Selection of signal function

^ 12.3−18

3Bh

3

Select signal function for
input E.1

4

Select signal function for
output E.0

01

h

5

Select signal function for
output E.1

6

Select options for input E.0

Bits 0 ... 3

Conversion speed

3)

Resolution

00

h

7

Select options for input E.1

0000

15 conversions/s

16 Bit

00

h

0001

30 conversions/s

16 Bit

0010

60 conversions/s

15 Bit

0011

123 conversions/s

14 Bit

0100

168 conversions/s

12 Bit

0101

202 conversions/s

10 Bit

0110

3.7 conversions/s

16 Bit

0111

7.5 conversions/s

16 Bit

Bits 4 ... 7

Reserved

8...11

Reserved

1)

The wire breakage detection is used in the measuring range 4 ... 20 mA. If the wire breakage detection is
activated in byte 0 and the diagnostic alarm is enabled, a current reduction to below 0.8 mA is indicated.

2)

If the diagnostic alarm is enabled in byte 0, diagnostic data are transmitted to the master via the emergency
telegram in the event of an error.

3)

The conversion speeds given are valid for the operation of an analog input. When operating several inputs, divide
the corresponding conversation speed by the number of active inputs to detect the conversion speed per input.
Please note that the resolution is reduced with higher conversion speeds due to shorter integration times. The
data transfer format remains the same. Only the lower bits (LSBs) are not relevant anymore for the analog value.

Advertising