The modular system, 8×digital input – Lenze EPM−T9XX Modular system User Manual

Page 48

Advertising
background image

8×digital input

4

The modular system

4.5

L

4.5−2

EDSPM−TXXX−9.0−11/2009

DI 8xDC24V

.0

.1

.2

.3

.4

.5

.6

.7

1

2

3

4

5

6

7

8

9

L

10

EPM – T210 1A

0

1

+

1

2

3

4

5

6

7

8

9

10

DC 24 V (DC 18 … 28.8 V)

.

epm−t025

epm−t026

Fig. 4.5−2

Front view and connection of 8×digital input

0

Status display .0 ... .7; LED (green) is
lit when a HIGH level is recognised

1

Terminal strip assignment details

1

Not assigned

2

Digital input E.0

3

Digital input E.1

4

Digital input E.2

5

Digital input E.3

6

Digital input E.4

7

Digital input E.5

8

Digital input E.6

9

Digital input E.7

10

GND (reference potential)

.

Connection to backplane bus

Type

8×digital input

Voltage supply

DC 5 V / 20 mA (via backplane bus)

Connectable cable cross−section

£ 2.5 mm

2

(

³ AWG 14)

Digital inputs

Rated input voltage

DC 24 V (DC 18 ... 28.8 V)

Number of inputs

8

Level

LOW: DC 0 ... 5 V
HIGH: DC 15 ... 30 V

Input resistance

3.3 k

W

Delay time

3 ms

Electrical isolation from backplane bus

Yes, via optocouplers

Communication

Input data

1 byte

Dimensions

Width

25.4 mm

Height

76.0 mm

Depth

76.0 mm

Weight

50 g

Order designation

EPM−T210

Status display and terminal
assignment

Technical data

Advertising