Parameterising analog modules

Parameter data

13

Parameter setting via PROFIBUS−DP

13.1

13.1.1

L

13.1−2

EDSPM−TXXX−9.0−11/2009

The following bytes with fixed assignment are available for parameter data:

Byte

Assignment

Lenze
setting

0

Enabling/inhibiting diagnostic
alarm

1)

Bits 0 ...
5 %

Reserved

00

h

Bit 6

0

Alarm inhibited

^ 12.3−6

1

Alarm enabled

Bit7

Reserved

1

Reserved

2

Selecting signal function for
input E.0

Selection of signal function

^ 13.1−7

3

Selecting signal function for
input E.1

4

Selecting signal function for
input E.2

5

Selecting signal function for
input E.3

6

Select options for input E.0

1)

Bits 0 ...
3

Conversion speed

2)

Resolution

00

h

7

Select options for input E.1

1)

0000
0001
0010
0011
0100
0101
0110
0111

15 conversions/s
30 conversions/s
60 conversions/s
123 conversions/s
168 conversions/s
202 conversions/s
3.7 conversions/s
7.5 conversions/s

16 Bit
16 Bit
15 Bit
14 Bit
12 Bit
10 Bit
16 Bit
16 Bit

00

h

8

Select options for input E.2

1)

00

h

9

Select options for input E.3

1)

00

h

Bits 4 ...
5 %

Data selection
00

Deactivated

01

Use 2 of 3 values

10

Use 4 of 6 values

Bits 6 ...
7

Hysteresis
00

Deactivated

01

Hysteresis ±8

10

Hysteresis ±16

1)

The function is not available for the modules 4×analog input ±10V and 4×analog input ±20mA.

2)

The conversion speeds given are valid for the operation of an analog input. When operating several inputs, the
corresponding conversion speed must be divided by the number of active inputs to detect the conversion speed
per input.
Please note that due to shorter integration times the resolution is reduced at higher conversion speeds. The data
transfer format remains the same. Only the lower bits (LSBs) no longer are relevant for the analog value.