background image

Parameterising 2/4xcounter module

Parameter data

13

Parameter setting via PROFIBUS−DP

13.2

13.2.1

L

13.2−1

EDSPM−TXXX−9.0−11/2009

13.2

Parameterising 2/4xcounter module

13.2.1

Parameter data

The operating mode of the 2/4xcounter (e.g. 2 x 32−bit counter or 4 x 16−bit
counter) can be determined by assigning each channel (counter 0 and counter 1)
a mode via the parameter data.

(

Stop!

Depending on the mode setting, the terminal assignment of the
counter module changes!

For the 2/4xcounter, 2 bytes of parameter data are available.

The parameter data follow the assignment below:

Byte

Assignment

Lenze setting

0

Mode, counter 0

Selecting the modes

00

h

1

Mode, counter 1

00

h

Counter mode overview

Mode of

Function

IN1

IN2

IN3

IN4

IN5

IN6

OUT0

OUT1

Auto

Reload

Compare

Load

[h]

[dec]

2 counters

0

1

00

h

0

32−bit counter

RES

CLK

DIR

RES

CLK

DIR

·

·

01

h

1

Encoder 1 edge

RES

A

B

RES

A

B

·

·

03

h

3

Encoder 2 edges

RES

A

B

RES

A

B

·

·

05

h

5

Encoder 4 edges

RES

A

B

RES

A

B

·

·

4 counters

0.1

0.2

1.1

1.2

08

h

8

2 × 16−bit counters
(counting direction up/up)

CLK

CLK

CLK

CLK

09

h

9

2 × 16−bit counters
(counting direction down/up)

CLK

CLK

CLK

CLK

0A

h

10

2 × 16−bit counters
(counting direction up/down)

CLK

CLK

CLK

CLK

0B

h

11

2 × 16−bit counters
(counting direction down/down)

CLK

CLK

CLK

CLK

2 counters

0

1

0C

h

12

2 × 32−bit counters
(counting direction up)

RES

CLK

GATE

RES

CLK

GATE

·

·

ü

0D

h

13

2 × 32−bit counters
(counting direction down)

RES

CLK

GATE

RES

CLK

GATE

·

·

ü

0E

h

14

2 × 32−bit counters
(counting direction up)

RES

CLK

GATE

RES

CLK

GATE

·

·

ь

ь

0F

h

15

2 × 32−bit counters
(counting direction down)

RES

CLK

GATE

RES

CLK

GATE

·

·

ь

ь

1 counter

0/1

10

h

16

Frequency measuring

RES

CLK

START

STOP

·

·

ü

11

h

17

Measuring the period

RES

CLK

START

STOP

·

·

ü

12

h

18

Frequency measuring
(Counter output on/off)

RES

CLK

START

STOP

·

·

ь

Advertising