Appendix, Index table – Lenze EPM−T9XX Modular system User Manual

Page 529

Advertising
background image

Index table

15

Appendix

15.1

L

15.1−15

EDSPM−TXXX−9.0−11/2009

Index

Important

Possible settings

Name

Selection

Lenze

I4103

h

*

SSI control

0

{1}

255 SSI interface module

·

Settings only apply to SSI mapping
standard 1 and 2 mode (I4104

h

= 1 and

2)

·

Counter value is set under I4101

h

^ 12.5−1

Bit

1 Module 1

0

0

SSI control setpoint selection I/O0 (LSB)

Bit value 0: No selection via I/O.x
Bit value 1: Selection via I/O.x

2 Module 2

0

1

SSI control setpoint selection I/O1

3 Module 3

0

2

Reserved

... ...

...

3

SSI control output condition 0 SSI > setpoint

Bit value 0: I/O.x is set 1, if counter value >
setpoint
Bit value 1: I/O.x is set 1, if counter value <
setpoint

8 Module 8

0

4 ... 7

Reserved

I4104

h

*

SSI mapping

0

Mapping for communication with Lenze
devices

^ 12.5−1

0

SSI mapping PLC

Data exchange with PLC units using the
function blocks "L_IOSSIDataToIO" and
"L_IOSSIDataFromIO".

1

SSI mapping standard 1

Data exchange with 9300 controllers using
the function blocks CAN−IN/CAN−OUT

2

SSI mapping standard 2

I6000

h

Digital input

0

{1}

255 Display only

Digital input status

^ 8.10−3

1 Module 1

2 Module 2

... ...

64 Module 64

I6002

h

¿

Change polarity
digital input

0

{1}

255 Inverts digital input signals

^ 12.2−1

1 Module 1

0

2 Module 2

0

... ...

...

64 Module 64

0

I6200

h

*

Digital output

0

{1}

255

·

Digital output status

·

The outputs can be set manually
(forcing):

– Depends on CAN status and I2360

h

^ 8.10−4

1 Module 1

2 Module 2

... ...

64 Module 64

I6202

h

¿

Change polarity
digital output

0

{1}

255 Inverts digital output signals

^ 12.2−1

1 Module 1

0

2 Module 2

0

... ...

...

64 Module 64

0

I6206

h

¿

Error mode digital
output

0

{1}

255 Configures digital output monitoring

For the compact system, only index I6206

h

,

subindex 1 is available

^ 8.9−2

0

All digital outputs retain the last status output.

255

Response from I6207

h

In I6207

h

, the response can be configured

individually for each digital output

1 Module 1

0

2 Module 2

0

... ...

...

64 Module 64

0