The identifiers of process data objects PDO1 ... PDO10 consist of the so−called
basic identifiers and the set node address:

Identifier = Basic identifier + node address

Basic identifier

Available for

dec

hex

CAN gateway

8×dig. I/O compact

16×dig. I/O compact
32×dig. I/O compact

PDOs

Process data object 1

ь

ь

PDO1−Rx

768

300

PDO1−Tx

767

2FF

Process data object 2

ü

PDO2−Rx

640

280

PDO2−Tx

639

27F

Process data object 3

ü

PDO3−Rx

512

200

PDO3−Tx

384

180

Process data object 4

ü

PDO4−Rx

832

340

PDO4−Tx

896

380

Process data object 5

ü

PDO5−Rx

1024

400

PDO5−Tx

448

1C0

Process data object 6

ü

PDO6−Rx

1088

440

PDO6−Tx

704

2C0

Process data object 7

ü

PDO7−Rx

1152

480

PDO7−Tx

960

3C0

Process data object 8

ü

PDO8−Rx

1280

500

PDO8−Tx

1216

4C0

Process data object 9

ü

PDO9−Rx

1344

540

PDO9−Tx

1728

6C0

Process data object 10

ü

PDO10−Rx

1664

680

PDO10−Tx

1984

7C0

Basic identifiers of the process