background image

Diagnostics

Diagnostic data

10

Networking via PROFIBUS−DP

10.6

10.6.2

L

10.6−3

EDSPM−TXXX−9.0−11/2009

The code−related diagnostic data contains information about the slot on which an
error has occurred.

l

The code−related diagnostics are activated via the parameter setting.

Byte

Assignment

Byte 1

Bit 5 ... 0

000010

Length of code−related diagnostic data

Bit 7, 6

01

Code for code−related diagnostics

Byte 2

Bit 7 ... 0

The corresponding bit is set to "1" if the following occurs on a slot

·

the module is disconnected,

·

a non−configured module is connected,

·

the module cannot be accessed,

·

the module reports a diagnostic alarm.

00000001

Module slot 1

00000010

Module slot 2

00000100

Module slot 3

00001000

Module slot 4

00010000

Module slot 5

00100000

Module slot 6

01000000

Module slot 7

10000000

Module slot 8

Byte 3

Bit 7 ... 0

00000001

Module slot 9

00000010

Module slot 10

...

...

10000000

Module slot 16

Byte 4

Bit 7 ... 0

00000001

Module slot 17

00000010

Module slot 18

...

...

10000000

Module slot 24

Byte 5

Bit 7 ... 0

00000001

Module slot 25

00000010

Module slot 26

...

...

10000000

Module slot 32