Parameterising 2/4xcounter module

2 x 32 bit counter with G/RES (mode 27)

12

Parameter setting via system bus (CAN) / CANopen

12.4

12.4.14

L

12.4−39

EDSPM−TXXX−9.0−11/2009

12.4.14

2 x 32 bit counter with G/RES (mode 27)

epm−t142

Fig. 12.4−51

Terminal assignment of the 2/4xcounter in the mode 27

The mode 27 offers two 32−bit counters which can be assigned with a starting
value.

The counting direction is determined via the signal level at input IN3 / IN6 (DIR):

Upcounter: LOW level
Downcounter: HIGH level

If a HIGH level is applied to input IN3 / IN6 (G/RES), the counter is incremented or
decremented by 1 with each LOW/HIGH edge.

During the counting process a HIGH level must be applied to input IN1 / IN4
(G/RES). With a LOW level the counter content is frozen. With a rising edge at the
input IN1 / IN4 (G/RES) the counter is deleted.

When the counter reaches zero, the output OUT0 / OUT1 is set to HIGH level for
at least 100 ms, even if the counter continues to count. When the counter stops
at zero, the output OUT0 / OUT1 remains on the HIGH level.

Terminal assignment

DIR signal

CLK signal

G/RES signal

OUT signal