Lenze EPM−T9XX Modular system User Manual

Page 382

Advertising
background image

Parameterising SSI interface

Process data assignment for "SSI mapping PLC" (I4104 = 0)

12

Parameter setting via system bus (CAN) / CANopen

12.5

12.5.3

L

12.5−6

EDSPM−TXXX−9.0−11/2009

12.5.3

Process data assignment for "SSI mapping PLC" (I4104 = 0)

This mapping is required for encoder value evaluation with Lenze PLC units and
function blocks of the "IO_System.lib".

Setting index I4104

h

= 0 (Lenze setting) adapts the input/output byte assignment

for communication with Lenze PLC units.

R
PDO

x

Data to module

Control

Dat

a

In

H

B

Dat

a

In

M

B

Dat

a

In

L

B

S

tatus

Dat

a

Out

HB

Dat

a

Out

MB

Dat

a

Out

LB

0

E/A.1

E/A.0

SSI

Encoder

0

1

1

2

2

3

3

4

4

5

5

6

6

7

7

Data from module

T
PDO

x

Gateway

SSI-Interface

L

.0

.1

.2

.3

.4

.5

.6

.7

1

2

3

4

5

6

7

8

9

L

10

PW

ER

RD

BA

ADR.

0

1

DC
24V

X1

+24 V

Hold

E/A.0

epm−t172

Fig. 12.5−8

Data input /output of SSI interface

For data input / output, four bytes are available which are transmitted (Rx PDO) or
output (Tx PDO) by PDOs.

)

Note!

Input and output data get lost when the mains supply is switched
off/on; they are not stored!

The Rx PDO contains the input data used to control the outputs (I/O.0 and I/O.1)
depending on the encoder value.

Byte

Assignment

0

Control

Bits 0 ... 1

Setpoint selection
00: No setpoint selection
01: Setpoint selection for output I/O.0
10: Setpoint selection for output I/O.1
11: Setpoint selection for outputs I/O.0 and I/O.1

Bit 2

Reserved

Bit 3

Condition for setting the output = HIGH
0: If SSI encoder value is higher than setpoint
1: If SSI encoder value is lower than setpoint

Bits 4 ... 7

Reserved

1

Comparison value (HIGH byte)

Bits 0 ... 7

Selection of comparison value

2

Comparison value (MID byte)

Bits 0 ... 7

3

Comparison value (LOW byte)

Bits 0 ... 7

The Tx PDO contains the output data supplied by the encoder.

Byte

Assignment

0

Status

Bit 0

Status I/O.0

Bit 1

Status I/O.1

Bits 2 ... 7

Reserved

1

SSI encoder value (HIGH byte)

Bits 0 ... 7

Output of SSI encoder value

2

SSI encoder value (MID byte)

Bits 0 ... 7

3

SSI encoder value (LOW byte)

Bits 0 ... 7

Input data

Output data

Advertising