13 parameter setting via profibus−dp – Lenze EPM−T9XX Modular system User Manual

Page 433

Advertising
background image

Parameterising analog modules

Signal functions of 4xanalog input /output

13

Parameter setting via PROFIBUS−DP

13.1

13.1.10

L

13.1−21

EDSPM−TXXX−9.0−11/2009

Paramete
r bytes
4/5

Signal function

Signal range

Format

1)

Tolerance

2)

00

h

Parameter data in module are not overwritten

01

h

Voltage signal
output

±10 V

−10.00
−16384

{0.01V}

{1

dec

}

+10.00

+16384

S5

Two’s

complement

±0.2 %

Min.

Limit

values

Max.

−12.50 V
−20480

dec

+12.50 V

+20480

dec

02

h

Voltage signal
output

1 ... 5 V

+1.00
0

{0.01V}

{1

dec

}

+5.00

+16384

S5

Two’s

complement

±0.6 %

Min.

Limit

values

Max.

0.00
−4096

dec

+6.00 V
+20480

dec

05

h

Voltage signal
output

0 ... 10 V

0.00
0

{0.01V}

{1

dec

}

+10.00

+16384

S5

Two’s

complement

±0.4 %

Min.

Limit

values

Max.

0.00
0

+12.50 V

+20480

dec

09

h

Voltage signal
output

±10 V

−10.00
−27648

{0.01V}

{1

dec

}

+10.00

+27648

S7

Two’s

complement

±0.2 %

Min.

Limit

values

Max.

−11.76 V
−32512

dec

+11.76 V

+32511

dec

0A

h

Voltage signal
output

1 ... 5 V

+1.00
0

{0.01V}

{1

dec

}

+5.00

+27648

S7

Two’s

complement

±0.6 %

Min.

Limit

values

Max.

0.00
−6912

dec

+5.704 V

+32511

dec

0D

h

Voltage signal
output

0 ... 10 V

0.00
0

{0.01V}

{1

dec

}

+10.00

+27648

S7

Two’s

complement

±0.4 %

Min.

Limit

values

Max.

0.00
0

+11.76 V

+32511

dec

03

h

Current signal
output

±20 mA

−20.00
−16384

{0.01 mA}

{1

dec

}

+20.00

+16384

S5

Two’s

complement

±0.3 %

Min.

Limit

values

Max.

−25.00 mA
−20480

dec

+25.00 mA

+20480

dec

04

h

Current signal
output

4 ... 20
mA

+4.00
0

{0.01 mA}

{1

dec

}

+20.00

+16384

S5

Two’s

complement

±0.8 %

Min.

Limit

values

Max.

+0.00
−4096

dec

+24.00 mA

+20480

dec