1 wiring according to emc, Wiring according to emc, Electrical installation – Lenze EPM−T9XX Modular system User Manual

Page 157

Advertising
background image

Wiring according to EMC

7

Electrical installation

7.1

L

7.1−1

EDSPM−TXXX−9.0−11/2009

7.1

Wiring according to EMC

General notes

·

The electromagnetic compatibility of the I/O system IP20 depends on the type and accuracy of the installation. Special attention should be
paid to:

– Assembly
– Shielding
– Earthing

·

Any other installation set−ups require the system to be checked for compliance with the EMC limit values for assessment of conformity with
the EMC Directive. This for instance applies to the following:

– Use of unshielded cables

·

Responsibility for compliance with the EMC Directive is with the user.

– It can be assumed, if the following measures are observed, that no EMC problems will arise during operation and that the EMC Directive

and / or the EMC Act, respectively, is complied with.

– Operating devices near the system that do not meet the CE standard in terms of disturbance immunity EN 61000−4−2, may cause

electromagnetic interference to these devices by the decentralised I/O system IP20.

Assembly

·

Connect DIN rail to earthed mounting plate:

– Mounting plates with conductive surfaces (zinc−coated or stainless steel) allow permanent contact.
– Painted plates are not suitable for installation in accordance with the EMC.

·

If you use several mounting plates:

– Connect the mounting plates electrically with a surface as large as possible (e.g. with copper bands).

·

When laying the cables, ensure spatial separation from signalling and mains cables.

·

Route the cables as close as possible to the reference potential. Freely suspended cables act like aerials.

Shielding

·

If possible, use only cables with braids.

·

The shield coverage should be in excess of 80%.

·

Data lines for serial coupling always require metallic or metallised plugs. Connect the shield of the data line to the plug housing.

·

Use metal cable clamps to attach the braids.

·

Connect shield to shield rail inside the switchgear cabinet.

·

Connect the shields of analog control cables at one end (either to the sensor or as closely as possible to the analog module input).

Earthing

·

Earth all metallically conductive components with suitable cables from a central earthing point (PE bar).

·

Comply with the minimum cross−sections defined in the safety instructions:

– It is not the cable cross−section that is decisive for EMC, but instead the cable surface and large−surface contact.

Advertising