Commissioning – Lenze EPM−T9XX Modular system User Manual

Page 289

Advertising
background image

System bus (CAN) / CANopen

Commissioning examples

11

Commissioning

11.1

11.1.2

L

11.1−5

EDSPM−TXXX−9.0−11/2009

When using the communication profile CANopen

1. Adapt the basic identifiers for the process data object 1.

– Set PDO1−Rx via index 1400

h

, and subindex 1 to 770.

– Set PDO1−Tx via index 1800

h

, and subindex 1 to 769.

2. Make a "reset node" by setting the index I2358

h

= 1. The settings are

accepted.

Setting of the baud rate and node address:

CANopen

Baud rate

Coding switch value

[kbit/s]

80

1000

81

500

82

250

83

125

84

100

85

50

86

20

87

10

88

800

Bold print = Lenze setting

1. Switch the CAN gateway module voltage supply off.

2. Use the coding switch to set the required baud rate.

– Select value 91.

3. Switch the CAN gateway module voltage supply on.

– The LEDs ER, RD and BA are blinking with a frequency of 1 Hz.

4. LEDs ER and BA go off after 5 seconds, and the set baud rate is stored.

5. Now set the node address 2 with the coding switch.

6. The set node address will be accepted after 5 seconds.

– LED RD goes off.

– The CAN gateway module changes to Pre−Operational status.

)

Note!

The node address can be changed any time with the coding
switch. The setting is accepted after switching on the supply
voltage.