Transmitting process data

Data transmission between I/O system IP20 and controller

9

Network via CANopen

9.3

9.3.8

L

9.3−11

EDSPM−TXXX−9.0−11/2009

9.3.8

Data transmission between I/O system IP20 and controller

In the Lenze setting of the I/O system IP20, the basic identifiers of the PDOs are
set for the communication protocol "system bus (CAN)".

For communicating with Lenze controllers the basic identifiers for the process data
object 1 must be adapted.

1. Set PDO1−Rx via index 1400

h

, subindex 1 to 770.

2. Set PDO1−Tx via index 1800

h

, subindex 1 to 769.

3. Make a reset node by setting the index I2358h = 1. The settings are

accepted.

l

L

EPM – T110 1A.10

PW

ER

RD

BA

ADR.

0

1

+

DC
24V

X1

DO 8xDC24V 1A

.0

L+

.1

.2

.3

.4

.5

.6

.7

F

1

2

3

4

5

6

7

8

9

L

10

EPM – T220 1A

DI 8xDC24V

.0

.1

.2

.3

.4

.5

.6

.7

1

2

3

4

5

6

7

8

9

L

10

EPM – T210 1A

PDO1-Rx

CAN_OUT3

CAN_IN3

PDO1-Tx

0

1



‚

ƒ

„

epm−t112

Fig. 9.3−2

Data transmission between I/O system IP20 and controller

PDO−Rx

The I/O system IP20 receives the status information of the controller

PDO−Tx

The I/O system IP20 transmits the status information to the controller

0

Controller with node address 1 (C0350 = 1)



768

d

(Basic identifier) + 1 (node address) = 769

d

(identifier)

‚

769

d

(Basic identifier) + 1 (node address) = 770

d

(identifier)

1

CAN gateway of the modular system (or a module of the compact system)
with node address 2

ƒ

767

d

(Basic identifier) + 2 (node address) = 769

d

(identifier)

„

768

d

(Basic identifier) + 2 (node address) = 770

d

(identifier)