System bus (CAN) / CANopen

Commissioning examples

11

Commissioning

11.1

11.1.2

L

11.1−3

EDSPM−TXXX−9.0−11/2009

Please also note relevant information on the controller in the System Manual!

Setting sequence:

1. Set CAN bus node address to value 1 (C0350 = 1).

2. Address for CAN3−IN and CAN3−OUT to be defined by C0350 (C0353/3 = 0).

3. Set CAN bus baud rate to 500 kbits/s (C0351 = 0).

4. Set CAN bus master operation (C0352 = 1).

5. Set cycle time for cyclical process data transfers (C0356/3 > 0).

6. Switch process output words in CAN3−OUT to digital output signals

(C0864/3 = 1).

7. Save set parameters (C0003 = 1).

8. Trigger CAN Reset Node (C0358 = 1).

)

Note!

When using an 8200 vector frequency inverter, make sure to set
the process data channel CAN−I/O from sync−controlled to
event−controlled transmission (C0360 = 0) .

The modified settings will be accepted after a "Reset Node"
(C0358 = 1).