PROFIBUS−DP

Wiring

7

Electrical installation

7.5

7.5.1

L

7.5−2

EDSPM−TXXX−9.0−11/2009

M

1

2

3

S

S

S

S

S

R

R

2133PFB004

Fig. 7.5−2

Number of nodes in the bus system PROFIBUS−DP

Segment

Master (M)

Slave (S)

Repeater (R)

1

1
2

31
30


2

31

1

3

30

2

)

Note!

Repeaters do not have a device address, but they are also
included in the calculation of the maximum slave number of
nodes.

Repeaters can be used to create line and tree topologies. The
maximum total extension of the bus system depends on

l

the used baud rate,

l

the number of repeaters.

Baud rate [kBit/s]

Length [m]

9.6 − 93.75

1200

187.5

1000

500

400

1500

200

3000 − 12000

100

Please follow our recommendations for signal cables.

Specification bus cable

Cable resistance

135 − 165

W/km, (f = 3 − 20 MHz)

Capacitance per unit length

£ 30 nF/km

Loop resistance

< 110

W/km

Core diameter

> 0.64 mm

Core cross−section

> 0.34 mm

2

Cores

Double twisted, insulated and shielded

Number of bus stations

Baud rate / length of bus cable

Specification of the transmission
cable