Parameterising SSI interface

Example of parameter setting via process data

12

Parameter setting via system bus (CAN) / CANopen

12.5

12.5.6

L

12.5−14

EDSPM−TXXX−9.0−11/2009

12.5.6

Example of parameter setting via process data

The station consists of a CAN gateway and an SSI interface. An encoder with a
24−bit resolution and Gray code is used.

Output I/O.0 is to switch with a counter value of > 1000, output I/O.1 with a counter
value of > 2000. For a simpler representation, the figures are provided in a
hexadecimal format.

Selection

Mapping

SSI mapping PLC (I4104

h

= 0)

Node address

2

Coding (I3001/1)

Gray code

Hold function (I3001/1)

Deactivated

1. Assigning parameter data

epm−t188

Fig. 12.5−17

Example − How to assign parameter data when using SSI interface

2. Assigning comparison value for channel 0

epm−t189

Fig. 12.5−18

Example − How to assign a comparison value to channel 0 when using SSI interface

3. Assigning comparison value for channel 1

epm−t190

Fig. 12.5−19

Example − How to assign a comparison value to channel 1 when using SSI interface