13 parameter setting via profibus−dp, Parameterising analog modules parameter data – Lenze EPM−T9XX Modular system User Manual

Page 415

Advertising
background image

Parameterising analog modules

Parameter data

13

Parameter setting via PROFIBUS−DP

13.1

13.1.1

L

13.1−3

EDSPM−TXXX−9.0−11/2009

l

For a 4×analog output module, 6 bytes of parameter data are available. The
following are defined via the parameter data

– The signal function for each output (current signal output, voltage signal

output),

– The module error behaviour.

l

The module can be parameterised with the configuration tool or via slot and
index.

– To set the parameters via slot and index, the function blocks SFB 52 (read)

and SFB 53 (write) are required.

Slot number

Index

Access

Description

1 ... 32

00

h

R

Read out diagnostic data record 0

W

Write parameters to the module

01

h

R

The corresponding diagnostic data record of the electronic module can be
read out via the index.

·

Example:

– Index 01

h

: read out diagnostic data record 1

– Index 02

h

: read out diagnostic data record 2

F1

h

R

Read out the module parameters

F2

h

R

Read out the process image of the module

R = read

W = write

The following bytes with fixed assignment are available for parameter data:

Byte

Assignment

Lenze setting

0

Enabling/inhibiting diagnostic
alarm

1)

Bits 0 ...
5 %

Reserved

00

h

Bit 6

0

Alarm inhibited

^ 12.3−6

1

Alarm enabled

Bit7

Reserved

1

Reserved

2

Selecting signal function for
output E.0

Selection of the signal function:

^ 13.1−14

3

Selecting signal function for
output E.1

4

Selecting signal function for
output E.2

5

Selecting signal function for
output E.3

1)

The function is not available for the modules 4×analog output ±10V and 4×analog output 0...20mA.

4xanalog output modules

Advertising