Parameterising 2/4xcounter module

Encoder (modes 1, 3, and 5)

13

Parameter setting via PROFIBUS−DP

13.2

13.2.4

L

13.2−10

EDSPM−TXXX−9.0−11/2009

The counter is incremented by 1 on

l

a LOW−HIGH edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).

l

a HIGH−LOW edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).

l

a LOW−HIGH edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).

l

a HIGH−LOW edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).

RES

B

A

Counter

00000000

XXXX

TreH2d

TcIH

TdL2cIH

TcIH2dH

TcIL

01

02

03

04

05

06

07

08

09

0A

0B

0C

0D

0E

0F

10

11

12

epm−t073

Fig. 13.2−12

Signal characteristic of 2/4xcounter in the mode 5 (upcounter)

The counter is decremented by 1 on

l

a LOW−HIGH edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).

l

a HIGH−LOW edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).

l

a LOW−HIGH edge at input IN2 / IN5 (A) and a LOW level at the input
IN3 / IN6 (B).

l

a HIGH−LOW edge at input IN2 / IN5 (A) and a HIGH level at input
IN3 / IN6 (B).

RES

B

A

Counter

00000000

FF

FE

FD

FC

FB

FA

F9

F8

F8

XXXX

TreH2d

F7

F6

F5

F4

TclL

TclH2dH

TdL2clH

TclH

F3

F2

F1

F0

EF

EE

epm−t074

Fig. 13.2−13

Signal characteristic of 2/4xcounter in the mode 5 (downcounter)

Signal characteristic in mode 5