background image

4×analog input

4

The modular system

4.14

L

4.14−3

EDSPM−TXXX−9.0−11/2009

(

Stop!

The module will be destroyed if the connected signals or encoders
do not match the set measuring range:

l

Max. 15 V input voltage in the voltage measuring range.

l

No input voltage in the resistance measuring range.

l

When the measuring range is changed, only assign the inputs
after the first gateway initialisation has been completed:
– During initialisation, the previous settings are still active.

Unsuitable input circuits may destroy the modules. Changes
will only become effective and permanently saved after
initialisation.

Two−wire connection

Four−wire connection

2

1

3

5

7

9

10

4

6

8

J

.

D

A

µP

MUX

PES

PES

PES

PES

PES

PES

PES

PES

D

A

µP

MUX

9

10

+U

+U

-U

-U

I

I

I

I

8

7

6

5

4

3

2

1

J

1

0

PES

PES

.

epm−t036

epm−t033

Fig. 4.14−3

Sensor connection

0

Analog input E.0

1

Analog input E.2

.

Connection to backplane bus

PES

HF shield termination through large−surface connection to PE

Sensor:

Voltage or current source

Thermal element

Resistor

J

Resistor, temperature−dependent

l

Short−circuit unused inputs (connect positive and negative terminals) or
deactivate them by setting parameters.

l

The module does not provide any auxiliary supply for sensors / actuators.
For information on how to connect an auxiliary supply, please see the
documentation for the sensors / actuators.