7 heartbeat, Heartbeat, Networking via system bus (can) – Lenze EPM−T9XX Modular system User Manual

Page 197

Advertising
background image

Heartbeat

8

Networking via system bus (CAN)

8.7

L

8.7−1

EDSPM−TXXX−9.0−11/2009

8.7

Heartbeat

COB-ID = 1792 + Node-ID

Heartbeat
Consumer

Heartbeat

Producer

indication

indication

indication

indication

indication

indication

indication

indication

Heartbeat Event

request

request

Heartbeat

Producer

Time

Heartbeat

Consumer

Time

Heartbeat

Consumer

Time

0

0

1

1

r

r

s

s

7

7

6 … 0

6 … 0

epm−t134

Fig. 8.7−1

Heartbeat Protocol

r

Reserved

s

State of the Heartbeat Producer

The I/O system IP20 can monitor up to five nodes. The status telegrams of the
nodes to be monitored must arrive cyclically within a certain time at the I/O system
IP20. If a status telegram is not received within this time, the I/O system IP20
switches to the status set in I1029

h

. The outputs switch to a defined status (also

see the chapter Configuration

® Diagnostics).

Settings are made in the index I1016

h

.

The I/O system IP20 assigns a status telegram to the fieldbus and can thus be
monitored by other nodes.

Settings are made in index I1017

h

.

l

Producer heartbeat is automatically started if a time > 0 is entered into the
index 1017

h

and the I/O system IP20 changes to the status "Operational".

l

After the cycle time has been completed, the status telegram is transmitted
to the fieldbus by the I/O system IP20.

l

A change to the Operational status triggers a reset.

Heartbeat Consumer

Heartbeat Producer