2 operating state of system bus (can), 3 reading out the module identifiers, 4 status of the digital inputs – Lenze EPM−T9XX Modular system User Manual

Page 207: Operating state of system bus (can), Reading out the module identifiers, Status of the digital inputs, Networking via system bus (can), Diagnostics operating state of system bus (can)

Advertising
background image

Diagnostics

Operating state of system bus (CAN)

8

Networking via system bus (CAN)

8.10

8.10.2

L

8.10−3

EDSPM−TXXX−9.0−11/2009

8.10.2

Operating state of system bus (CAN)

Index I2359

h

displays the operating status of the system bus.

I2359

h

Operating status

Description

0

Operational

The system bus is fully functional. The I/O system can transmit and receive parameter and process data.

1

Pre−Operational

The I/O system can transmit and receive parameter data while process data are ignored.
The status can be changed from

Pre−Operational to Operational by:

·

The CAN master

·

An NMT telegram ’00 01 00’

2

Warning

The I/O system has received incorrect telegrams and becomes passive in the overall system bus environment, i. e., the I/O
system can no longer transmit data.
Possible causes:

·

A missing bus termination

·

Insufficient shielding

·

Potential differences in the earth connections for the control electronics

·

The bus load is too high

3

Bus off

The I/O system has disconnected itself from the system bus after receiving too many incorrect telegrams.

Index

Name

Possible settings

Important

Lenze

Selection

I2359

h

CAN state

0

{1}

3 Display only

System bus status

^ 8.10−3

0
1
2
3

Operational
Pre−Operational
Warning
Bus off

8.10.3

Reading out the module identifiers

When using the modular system, the number of the modules connected to the
backplane bus as well as the module types used can be read out via index I1027

h

.

Each module type can be clearly identified via a hexadecimal value.

Index

Subindex

Reading...

Module type

Module identifier

0

... the number of plugged modules (0 ... 32)

0

h

... 20

h

I1027

h

1 ... 32

... the module type in slots 1 ... 32

No module

0

h

8×digital input

9FC1

h

16×digital input

9FC2h

1×counter/16×digital input

08C0h

8×digital output 1A
16×digital output 1A
8×digital output 2A
4×relay

AFC8

h

8×digital input / output

BFC9

h

4×analog input

15C4h

4×analog output

A5E0

h

4×analog input / output

45DB

h

2/4×counter

B5F4

h

SSI interface

B5DB

h

8.10.4

Status of the digital inputs

Via the index I6000

h

the status of the digital inputs can be displayed.

Advertising