Transmitting process data

Process image of the modular system

8

Networking via system bus (CAN)

8.3

8.3.5

L

8.3−7

EDSPM−TXXX−9.0−11/2009

In the I/O system shown in the example, the transmission time of the input signals
at the module M3 (8×digital input) to the master is to be detected. The baud rate
amounts to 500 kbits/s.

Solution:

l

For transmitting the input signals, the module assigns one byte (byte 3) of
the process data channel PDO1−Tx.

l

The delay time t

d

within the module amounts to 3 ms.

1. Calculating the time required for copying t

c

into the CAN object directory:

t

c

+ 50 ms ) 1 @ 25 ms + 75 ms

2. Calculating the transmission time t

t

of the input signals to the fieldbus:

t

t

+ 75 ms ) (1 @ 8 ms) ) (0 @ 2 ms) ) 3000 ms ) 742 ms + 3825 ms

3. Calculating the transmission time t

CAN

via the fieldbus:

l

L

EPM – T110 1A.10

PW

ER

RD

BA

ADR.

0

1

+

DC
24V

X1

DI 8xDC24V

.0

.1

.2

.3

.4

.5

.6

.7

1

2

3

4

5

6

7

8

9

L

10

EPM – T210 1A

t

CAN

epm−t135

t

CAN

+

CAN telegram length

Baud rate

+ 111 bits

500 kbits

s

+ 222 ms

4. Calculating the total transmission time t:

t

+ t

t

) t

CAN

+ 3825 ms ) 222 ms + 4047 ms + 4.047 ms

)

Note!

The internal processing times of the controller must also be
considered.