Transmitting process data

Process image of the modular system

8

Networking via system bus (CAN)

8.3

8.3.5

L

8.3−6

EDSPM−TXXX−9.0−11/2009

Process image

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

PDO1

Fixed for the first
DIO

PDO1−RX

M6

PDO1−TX

M1

M2

M3

M4

M5

M5

PDO2

Fixed for the first
AIO

PDO2−RX

M8

M8

M8

M8

M8

M8

M8

M8

PDO2−TX

M7

M7

M7

M7

M7

M7

M7

M7

PDO3

DIO or AIO

1)

PDO3−RX

M8

M8

M11

M11

M11

M11

PDO3−TX

M8

M8

M8

M8

M8

M8

M8

M8

PDO4

DIO or AIO

1)

PDO4−RX

PDO4−TX

M8

M8

M11

M11

M11

M11

PDO5

DIO or AIO

1)

PDO5−Rx

M10

M10

M10

M10

M10

M10

PDO5−Tx

M10

M10

M10

M10

M10

M10

PDO6

DIO or AIO

1)

PDO6−Rx

M9

M9

M9

M9

PDO6−Tx

M9

M9

M9

M9

...

...

...

...

...

...

...

...

...

...

...

PDO10

DIO or AIO

1)

PDO10−RX

PDO10−TX

1)

A PDO can be either assigned to AIO or DIO.
The modules are assigned according to the slot
sequence, with the DIO being assigned first.

AI

Analog input data

AO

Analog output data

DI

Digital input data

DO

Digital output data

AIO

Analog input and output data

DIO

Digital input and output data

Special features of the modules 1×counter/16×digital input and SSI interface:

l

The module 1×counter/16×digital input always assigns the next to last and
the SSI interface module always the last of the PDOs used.

l

The modules cannot be assigned to PDO1 and PDO2. Thus, only eight of
these modules can be used in a system.

l

The modules assign a whole PDO (8 bytes) each.

The transmission times of the input / output signals within the I/O system IP20 can
be calculated with a formula.

t

t

+ t

c

) (N

PDOTX

@ 8 ms) ) (N

PDORX

@ 2 ms) ) t

d

) 742 ms

t

t

Transmission time of input / output signals of a module between
fieldbus connection and input / output terminals.

t

c

Time required for copying into the CAN object directory

N

PDOTX

Transmitting the PDO number (PDO1−Tx ... PDO10−Tx)

N

PDORX

Receiving the PDO number (PDO1−Rx ... PDO10−Rx)

t

d

Module delay time

742

ms

Fixed internal processing time

Time required for copying into the CAN object directory:

DO modules

DI modules

AO modules

AI modules

t

c

= 50

ms + n × 14 ms

t

c

= 50

ms + n × 25 ms

t

c

= 50

ms + n × 210 ms t

c

= 50

ms + n × 250 ms

n

Number of bytes assigned by the module in the PDOs

Transmission times