Parameterising 1xcounter/16xdigital input module

Parameter data

12

Parameter setting via system bus (CAN) / CANopen

12.6

12.6.1

L

12.6−1

EDSPM−TXXX−9.0−11/2009

12.6

Parameterising 1xcounter/16xdigital input module

12.6.1

Parameter data

The parameter data can be used to assign a mode to the internal counter and to
configure the digital input filter.

For the 1xcounter/16xdigital input, three bytes of parameter data are available,
which are assigned via SDOs.

Parameter setting via Global Drive Control (GDC):

Depending on the plug−in station, the module is parameterised via the indices
3001

h

... 3010x

h

(maximum 8 counter modules). The parameter data is stored in

the subindex 1.

Parameter setting via CoDeSys:

The max. 8 counter modules are addressed via index I3401

h

. The parameter data

are assigned in the subindices 1 ... 64 (4 bytes per subindex). The counter module
assigns 1 subindex.

Index

Subindex

1

00

h

00

h

00

h

00

h

I3xxx

h

Byte 0

Byte 1

Byte 2

epm−t176

Fig. 12.6−1

Display of the parameter data of 1xcounter/16xdigital input

The parameter data follows the assignment below:

Byte

Assignment

Lenze setting

0

Counter mode

00

h

Encoder with 4 edges

00

h

01

h

32−bit counter

02

h

Clock up/clock down evaluation

03

h

Measuring the frequency

04

h

Measuring the period

05

h

... FF

h

Reserved

1

Filter factor A

0 ... 255

Configuration of the digital input filters for
counter inputs E.0 and E.1

00

h

2

Filter factor B

0 ... 255

00

h

)

Note!

Store changed parameters in the EEPROM via index I2003

h

. The

settings are maintained after switching off the supply voltage.