System bus (CAN) / CANopen

Commissioning examples

11

Commissioning

11.1

11.1.2

L

11.1−4

EDSPM−TXXX−9.0−11/2009

If you use the communication profile system bus (CAN)

Setting of the baud rate and node address:

System bus (CAN)

Baud rate

Coding switch value

[kbit/s]

90

1000

91

500

92

250

93

125

94

100

95

50

96

20

97

10

98

800

Bold print = Lenze setting

1. Switch the CAN gateway module voltage supply off.

2. Use the coding switch to set the required baud rate.

– Select value 91.

3. Switch the CAN gateway module voltage supply on.

– The LEDs ER, RD and BA are blinking with a frequency of 1 Hz.

4. LEDs ER and BA go off after 5 seconds, and the set baud rate is stored.

5. Now set the node address 2 with the coding switch.

6. The set node address will be accepted after 5 seconds.

– The LED RD goes off.

– The CAN gateway module changes to Pre−Operational status.

)

Note!

The node address can be changed any time with the coding
switch. The setting is accepted after switching on the supply
voltage.