Parameterising digital modules

Parameter data

12

Parameter setting via system bus (CAN) / CANopen

12.2

12.2.1

L

12.2−1

EDSPM−TXXX−9.0−11/2009

12.2

Parameterising digital modules

12.2.1

Parameter data

Via the parameter data of the digital modules it can be defined how the control
signals are to be transmitted: with original polarity or inverse polarity.

1 byte (8x module) or 2 bytes (16x modules) are available for parameter data, which
are assigned via SDOs.

l

Digital inputs are parameterised via the index I6002

h

.

l

Digital outputs are parameterised via the index I6202

h

.

The subindex depends on the plug−in station (max. 32 digital modules).

epm−t174

Fig. 12.2−1

Display of the parameter data "digital module"

Byte

Assignment

Lenze setting

0

Polarity of the transmitted
signals

Bit 0

0

Signal is transmitted in original
form

00

h

1

Signal is transmitted in inverse
form

Bits 1 ... 7

Reserve

)

Note!

Store changed parameters in the EEPROM via index I2003

h

. The

settings are maintained after switching off the supply voltage.

8xdigital input module
8xdigital output module
8xdigital input/output module
16xdigital input module
16xdigital output module