The compact system, 16×dig. i/o compact (three−wire conductor) – Lenze EPM−T9XX Modular system User Manual

Page 134

Advertising
background image

16×dig. I/O compact (three−wire conductor)

5

The compact system

5.3

L

5.3−4

EDSPM−TXXX−9.0−11/2009

LED

Status

Meaning

PW (yellow)

on

Supply voltage is applied

ER (red)

on

Incorrect data transmission between microcontroller and digital inputs/outputs

RD (green)

on

Error−free data transmission between microcontroller and digital inputs/outputs

See table below

BA (yellow)

See table below

PW (yellow)

ER (red)

RD (green)

BA (yellow)

Meaning

on

off

blinking (1 Hz)

off

Self test and initialisation in progress

on

off

on

on

System bus (CAN)/CANopen in the
"Operational"state

on

off

on

blinking (1 Hz)

System bus (CAN)/CANopen in the
"Pre−Operational"state

on

off

on

blinking (10 Hz)

System bus (CAN)/CANopen in the
"Stopped"state

on

blinking (10 Hz)

on

on

blinking (1 Hz)

blinking (10 Hz)

System bus (CAN)/CANopen "Offline"state

on

blinking (1 Hz)

on

System bus (CAN)/CANopen "Warning"state

on

on

on

on

Error during RAM or EEPROM initialisation

on

blinking (1 Hz)

blinking (1 Hz)

blinking (1 Hz)

Baud rate setting mode active

on

blinking (10 Hz) blinking (10 Hz) blinking (10 Hz) Error during baud rate setting

on

off

blinking (1 Hz)

off

Address setting mode active

)

Note!

NMT telegrams for changing to the different states can be found in
the chapter "Networking via system bus (CAN)" or "Networking via
CANopen".

Status displays