Parameterising analog modules parameter data – Lenze EPM−T9XX Modular system User Manual

Page 300

Advertising
background image

Parameterising analog modules

Parameter data

12

Parameter setting via system bus (CAN) / CANopen

12.3

12.3.1

L

12.3−2

EDSPM−TXXX−9.0−11/2009

The following bytes with fixed assignment are available for parameter data:

Byte

Assignment

Lenze
setting

0

Enable / inhibit diagnostic
alarm

1) 3)

Bits 0 ... 5

Reserved

00

h

Bit 6

0

Alarm inhibited

^ 12.3−6

1

Alarm enabled

Bit 7

Reserved

1

Reserved

2

Select signal function for
input E.0

Selecting the signal function for analog inputs:

^ 12.3−8

3Bh

3

Select signal function for
input E.1

3Bh

4

Select signal function for
input E.2

3Bh

5

Select signal function for
input E.3

3Bh

6

Select options for input E.0

3)

Bits 0 ... 3

Conversion speed

2)

Resolution

00

h

7

Select options for input E.1

3)

0000
0001
0010
0011
0100
0101
0110
0111

15 conversions/s
30 conversions/s
60 conversions/s
123 conversions/s
168 conversions/s
202 conversions/s
3.7 conversions/s
7.5 conversions/s

16 bits
16 bits
15 bits
14 bits
12 bits
10 bits
16 bits
16 bits

00

h

8

Select options for input E.2

3)

00

h

9

Select options for input E.3

3)

00

h

Bits 4 ... 5

Data selection
00

Deactivated

01

Use 2 of 3 values

10

Use 4 of 6 values

Bits 6 ... 7

Hysteresis
00

Deactivated

01

Hysteresis ±8

10

Hysteresis ±16

1)

If the diagnostic alarm is enabled in byte 0, diagnostic data are transmitted to the master via the emergency
telegram in the event of an error.

2)

The conversion speeds given are valid for the operation of an analog input. When operating several inputs, the
corresponding convervion speed must be divided by the number of active inputs to detect the conversion speed
per input.
Please note that the resolution is reduced with higher conversion speeds due to shorter integration times. The
data transfer format remains the same. Only the lower bits (LSBs) are not relevant anymore for the analog value.

3)

The function is not available for the modules 4xanalog input ±10V and 4xanalog input ±20mA.