10 signal functions 4xanalog output 0 ma, Signal functions 4xanalog output 0 ma – Lenze EPM−T9XX Modular system User Manual

Page 315

Advertising
background image

Parameterising analog modules

Signal functions 4xanalog output 0...20mA

12

Parameter setting via system bus (CAN) / CANopen

12.3

12.3.10

L

12.3−17

EDSPM−TXXX−9.0−11/2009

12.3.10

Signal functions 4xanalog output 0...20mA

)

Note!

In the event of an overflow or underflow, wrong values are output.
Strong signal jumps with sign reversal may occur.

Paramete
r bytes
2/3/4/5

Signal function

Signal range

Format

1)

Tolerance

00

h

15

No signal emitted at output

01

h

06

h

Current signal
output

0 ... 20
mA

0.00
0

{0.01 mA}

{1

dec

}

+20.00

16384

S5

Two’s

complement

±0.2 %

2)

±0.4 %

3)

Min.

Limit

values

Max.

0.00
0

+25.00 mA

+20480

dec

04

h

Current signal
output

4 ... 20
mA

4.00
0

{0.01 mA}

{1

dec

}

20.00

16384

S5

Two’s

complement

±0.3 %

2)

±0.5 %

3)

Min.

Limit

values

Max.

0.00
−4096

dec

+24.00 mA

+20480

dec

0C

h

Current signal
output

4 ... 20
mA

4.00
0

{0.01 mA}

{1

dec

}

20.00

27648

S7

Two’s

complement

±0.3 %

2)

±0.5 %

3)

Min.

Limit

values

Max.

0.00
−6912

dec

+22.81 mA

+32511

dec

0E

h

Current signal
output

0 ... 20
mA

0.00
0

{0.01 mA}

{1

dec

}

20.00

27648

S7

Two’s

complement

±0.2 %

2)

±0.4 %

3)

Min.

Limit

values

Max.

0.00
0

+23.52 mA

+32511

dec

FF

h

Analog output is switched off

1)

Format of the output data (

12.3−7).

2)

Tolerance of the output range at an ambient temperature of 25 °C.

3)

Tolerance of the output range across the entire admissible temperature range.

Lenze setting of the signal function in parameter bytes 2 and 3 or 4 and 5: 06

h