Setting of baud rate and node address (node ID)

8

Networking via system bus (CAN)

8.5

L

8.5−1

EDSPM−TXXX−9.0−11/2009

8.5

Setting of baud rate and node address (node ID)

Baud rate

For establishing communication, all devices must use the same baud rate for the
data transfer.

l

The baud rate can be set via the coding switch at the module.

Node address

Each node of the network must be assigned to a node address, also called Node ID
within a range of 1 ... 63 for clear identification.

l

A node address in a network may be used only once.

l

The node address must be set with the coding switch at the module.

0 1

+ +

– –

epm−t024

Fig. 8.5−1

Coding switch at CAN gateway

Decrease numerical value

+

Increase numerical value

System bus (CAN)

Baud rate

Coding switch value

[kbit/s]

90

1000

91

500

92

250

93

125

94

100

95

50

96

20

97

10

98

800

Bold print = Lenze setting

1. Switch off the voltage supply of the module.

2. Use the coding switch to set the required baud rate.

– Select "9x" (x = value for the required baud rate)

3. Switch on the voltage supply of the module.

– The LEDs ER, RD and BA are blinking with a frequency of 1 Hz.

4. LEDs ER and BA go off after 5 seconds, and the set baud rate is stored.

Baud rate setting