Parameterising 2/4xcounter module

2 x 32 bit counter with GATE (mode 35)

13

Parameter setting via PROFIBUS−DP

13.2

13.2.18

L

13.2−50

EDSPM−TXXX−9.0−11/2009

13.2.18

2 x 32 bit counter with GATE (mode 35)

epm−t160

Fig. 13.2−67

Terminal assignment of the 2/4xcounter in the mode 35

The mode 35 offers two 32−bit counters which can be assigned with a starting
value.

The counting direction is determined via the signal level at input IN3 / IN6 (DIR):

Upcounter: LOW level
Downcounter: HIGH level

Each LOW−HIGH edge at input IN2 / IN5 (CLK) increments and/or decrements the
counter by 1, respectively.

During the counting process, a HIGH level must be applied to input IN1 / IN4
(GATE). With a LOW level the counter content is frozen.

When the counter reaches zero, the output OUT0 / OUT1 is set to HIGH level for
at least 100 ms, even if the counter continues to count. When the counter stops
at zero, the output OUT0 / OUT1 remains on the HIGH level.

Terminal assignment

DIR signal

CLK signal

GATE signal

OUT signal