13 parameter setting via profibus−dp, Parameterising ssi interface parameter data – Lenze EPM−T9XX Modular system User Manual

Page 492

Advertising
background image

Parameterising SSI interface

Parameter data

13

Parameter setting via PROFIBUS−DP

13.3

13.3.1

L

13.3−2

EDSPM−TXXX−9.0−11/2009

The parameter data is assigned as follows:

Byte

Assignment

Lenze setting

0

Reserved

1

Reserved

2

Baud rate

1)

00

h

= 300 kBaud

00

h

01

h

= 100 kBaud

02

h

= 300 kBaud

03

h

= 600 kBaud

04

h ...

FF

h

= 300 kBaud

3

Coding

2)

Bit 0

0

Binary code

00

h

1

Gray code

Bit 1

Reserved

Hold function

3)

Bit 2

0

Deactivate

1

Activate

Bits 3 ...
7

Reserved

1)

The encoder connected to the SSI interface transmits serial data. Therefore the encoder receives a clock pulse
from the SSI interface. The clock pulse is determined by you.

2)

If the encoder transmits the data in Gray code to the SSI interface, activate the Gray code to ensure that the data
will be transferred in binary code from the gateway.

3)

If the hold function is activated, the current encoder value will be frozen as soon as +24 V are applied to the input
I/O.0 +24 V. For this, the switching function must be parameterised for the input I/O.0.

)

Note!

The baud rate depends on the cable length and the SSI encoder.
The cables must be twisted and shielded in pairs. The following
data serve as a guideline:

Cable length

Baud rate

< 400 m

100 kBaud

< 100 m

300 kBaud

< 50 m

600 kBaud