The modular system, Can gatewayeco – Lenze EPM−T9XX Modular system User Manual

Page 36

Advertising
background image

CAN GatewayECO

4

The modular system

4.2

L

4.2−2

EDSPM−TXXX−9.0−11/2009

l

Use the coding switch to set the baud rate.

l

The node address must be set via the coding switch.

Coding
switch

64
32
16
8
4
2
1
L/C

1

0

Value

0

1

2

3

4

5

6

7

8

Baud rate [kBit/s]

1000

500

250

125

100

50

20

10

800

Bold print = Lenze setting

1. Switch off the voltage supply of the module.

2. Set all switches to "0" (not switch "L/C") on the coding switch.

3. Switch on the voltage supply of the module.

– The LEDs ER, RD and BA blink with a frequency of 1 Hz.

4. Set the desired baud rate with the coding switch. You have 10 seconds time.

– LEDs ER and BA go off after 10 seconds, and the set baud rate is stored.

5. You have a further 10 seconds time to set the node address.

Coding
switch

64
32
16
8
4
2
1
L/C

1

0

...

Node address

1

2

3

4

5

6

7

...

63

6. Set the node address for the module with the coding switch.

– Allowed device addresses are 1 ... 63.

– Each node address must be assigned only once.

– If the entered address is valid, the LED RD is extinguished and the

Gateway module changes to the pre−operational mode. The set address is
saved.

– If the entered address is invalid, the LEDs ER, RD and BA blink with a

frequency of 10 Hz.

)

Note!

l

The node address can be changed any time with the coding
switch. The setting is accepted after switching on the supply
voltage.

l

After switching on the supply voltage, the modular system
needs approx. 10 s for initialisation. During this time, the
modules cannot be parameterised.

Baud rate and node address

Setting the baud rate

Node address setting