Monitoring

Digital output monitoring

9

Network via CANopen

9.9

9.9.3

L

9.9−3

EDSPM−TXXX−9.0−11/2009

9.9.3

Monitoring of the analog outputs

Via the index I6443

h

you can configure the reactions of the analog outputs which

are to take place when no telegrams, "node guarding events" or "heartbeat" have
been received in the adjusted monitoring time.

l

Monitoring is started on receipt of the next PDO telegram after the settings.

l

If a telegram is not transmitted within the adjusted time, the module
switches to the "Pre−Operational" state. No further process data are
transmitted.

l

A change into the "Operational" state triggers a reset.

Index

Name

Possible settings

Important

Lenze

Selection

I6443

h

¿

Error mode analog
output

0

{1}

255 Configures analog output monitoring

Index is only available in the modular
system

^ 9.9−3

0

All analog outputs retain the last value output

255

Response from I6444

h

In I6444

h

the response can be configured

individually for each analog output

1 Channel 1

0

2 Channel 2

0

... ...

...

36 Channel 36

0

Via index I6444

h

the response can be configured individually for each analog

output.

Index

Name

Possible settings

Important

Lenze

Selection

I6444

h

¿

Error value analog
output

−32768

{1}

32767 Configures the individual analog output

responses
The analog outputs provide the set value
Index is only available in the modular
system

^ 9.9−3

1 Channel 1

0

2 Channel 2

0

... ...

...

36 Channel 36

0

Individual response setting