The modular system, 8×digital output 1a – Lenze EPM−T9XX Modular system User Manual

Page 56

Advertising
background image

8×digital output 1A

4

The modular system

4.9

L

4.9−2

EDSPM−TXXX−9.0−11/2009

DO 8xDC24V 1A

.0

L+

.1

.2

.3

.4

.5

.6

.7

F

1

2

3

4

5

6

7

8

9

L

10

EPM – T220 1A

1

2

0

3

1

2

3

4

5

6

7

8

9

10

.

Z
Z
Z
Z
Z
Z
Z
Z

+

DC 2

4 V

(DC 18
… 35 V)

epm−t017

epm−t016

Fig. 4.9−2

Front view and connection of 8×digital output 1A

0

Status display L+; LED (yellow) is lit
when a supply voltage is applied

3

Terminal strip assignment
details

1

DC 24 V supply voltage

2

Digital output A.0

1

Status display .0 ... .7; LED (green) is
lit when the corresponding output is
triggered

3

Digital output A.1

4

Digital output A.2

5

Digital output A.3

2

Status display F; LED (red) is lit in
case of overload, overheating or
short circuit

6

Digital output A.4

7

Digital output A.5

8

Digital output A.6

9

Digital output A.7

10

GND (reference potential)

.

Connection to backplane bus

Z

Load

Type

8×digital output 1A

Voltage supply

DC 5 V / 50 mA (via backplane bus)

Connectable cable cross−section

£ 2.5 mm

2

(

³ AWG 14)

Digital output data

Rated load voltage

DC 24 V (DC 18 ... 35 V)

Number of outputs

8

Max. output current per output

1 A (sustained short−circuit−proof)

Delay time

< 1 ms

Electrical isolation from backplane bus

Yes, via optocouplers

Communication

Output data

1 byte

Dimensions

Width

25.4 mm

Height

76.0 mm

Depth

76.0 mm

Weight

50 g

Order designation

EPM−T220

Status display and terminal
assignment

Technical data

Advertising