The modular system, 4×analog input / output, Stop – Lenze EPM−T9XX Modular system User Manual

Page 94: No input voltage in the resistance measuring range, Unused outputs remain unassigned

Advertising
background image

4×analog input / output

4

The modular system

4.20

L

4.20−2

EDSPM−TXXX−9.0−11/2009

(

Stop!

The module will be destroyed if the connected signals or encoders
do not match the set measuring range:

l

Max. 15 V input voltage in the voltage measuring range.

l

No input voltage in the resistance measuring range.

l

When the measuring range is changed, only assign the inputs
after the first gateway initialisation has been completed:
– During initialisation, the previous settings are still active.

Unsuitable input circuits may destroy the modules. Changes
will only become effective and permanently saved after
initialisation.

AI/AO 2/2x12BIT

+0

M0

+1

M1

Q0

M0

Q1

M1

F

L+

L

EPM – T330 1A. 10

0

1

2

3

4

5

6

7

8

9

10

1

.

D

A

D

A

µP

2

1

3

5

7

9

10

4

6

8

PES

PES

PES

PES

PES

PES

PES

PES

+

DC 24 V
(DC 20.4
… 28.8 V)

MUX

D

A

epm−t127

epm−t123

Fig. 4.20−2

Front view and connection of 4×analog input / output

0

Status display F; LED (red) is lit in
case of the following faults:

No external supply voltage

Wire breakage in the current
measuring range

1

Terminal strip assignment details
1

DC 24 V supply voltage

2

+ analog input E.0

3

− analog input E.0

4

+ analog input E.1

5

− analog input E.1

6

Analog output A.0

Input resistance of actuator

8

Analog output A.1

Sensor (voltage or current source)

7, 9 GND (reference potential for

analog signals)

PES HF shield termination through

large−surface connection to PE

10

GND (reference potential for
supply voltage)

.

Connection to backplane bus

l

Short−circuit unused inputs (connect positive and negative terminals) or
deactivate them by setting parameters.

l

Ensure correct polarity when connecting the actuators.

l

Unused outputs remain unassigned.

l

The module does not provide any auxiliary supply for sensors / actuators.
For information on how to connect an auxiliary supply, please see the
documentation for the sensors / actuators.

Status display and terminal
assignment