Parameterising analog modules

Signal functions of 4xanalog output ±10

12

Parameter setting via system bus (CAN) / CANopen

12.3

12.3.9

L

12.3−16

EDSPM−TXXX−9.0−11/2009

12.3.9

Signal functions of 4xanalog output ±10

)

Note!

In the event of an overflow or underflow, wrong values are output.
Strong signal jumps with sign reversal may occur.

Paramete
r bytes
2/3/4/5

Signal function

Signal range

Format

1)

Tolerance

00

h

14

No signal emitted at output

01

h

Voltage signal
output

±10 V

−10.00
−16384

{0.01V}

{1

dec

}

+10.00

16384

S5

Two’s

complement

±0.1 %

2)

±0.2 %

3)

Min.

Limit

values

Max.

−12.50 V
−20480

dec

+12.50 V
20480

dec

05

h

Voltage signal
output

0 ... +10
V

0.0
0

{0.1V}

{1

dec

}

+10.0

16384

S5

Two’s

complement

±0.2 %

2)

±0.4 %

3)

Min.

Limit

values

Max.

0.0
0

+12.5 V

20480

dec

09

h

Voltage signal
output

±10 V

−10.00
−27648

{0.01V}

{1

dec

}

+10.00 V
27648

dec

S7

Two’s

complement

±0.1 %

2)

±0.2 %

3)

Min.

Limit

values

Max.

−11.76 V
−32512

dec

+11.76 V
32511

dec

0D

h

Voltage signal
output

0 ... +10
V

0.0
0

{0.1V}

{1

dec

}

+10.0

27648

S7

Two’s

complement

±0.2 %

2)

±0.4 %

3)

Min.

Limit

values

Max.

0.0
0

+11.76 V
32511

dec

FF

h

Analog output is switched off

1)

Format of the output data (

12.3−7).

2)

Tolerance of the output range at an ambient temperature of 25 °C.

3)

Tolerance of the output range across the entire admissible temperature range.

Lenze setting of the signal function in parameter bytes 2 and 3 or 4 and 5: 01