3 2 x 32 bit counter (mode 0), 2 x 32 bit counter (mode 0), 13 parameter setting via profibus−dp – Lenze EPM−T9XX Modular system User Manual

Page 439

Advertising
background image

Parameterising 2/4xcounter module

2 x 32 bit counter (mode 0)

13

Parameter setting via PROFIBUS−DP

13.2

13.2.3

L

13.2−5

EDSPM−TXXX−9.0−11/2009

13.2.3

2 x 32 bit counter (mode 0)

epm−t064

Fig. 13.2−2

Terminal assignment of the 2/4xcounter in the mode 0

The mode 0 offers two 32−bit counters which can be assigned with a starting value.

Each LOW−HIGH edge at input IN2 / IN5 (CLK) increments and/or decrements the
counter by 1, respectively.

The counting direction is determined via the signal level at input IN3 / IN6 (DIR):

Upcounter: LOW level
Downcounter: HIGH level

During the counting process, a LOW level must be applied to input IN1 / IN4 (RES).
A HIGH level deletes the counter.

When the counter reaches zero, the output OUT0 / OUT1 is set to HIGH level for
at least 100 ms, even if the counter continues to count. When the counter stops
at zero, the output OUT0 / OUT1 remains on the HIGH level.

Terminal assignment

CLK signal

DIR signal

RES signal

OUT signal