Lenze EPM−T9XX Modular system User Manual

Page 385

Advertising
background image

Parameterising SSI interface

Process data assignment for "SSI mapping standard 1" (I4104 = 1)

12

Parameter setting via system bus (CAN) / CANopen

12.5

12.5.4

L

12.5−9

EDSPM−TXXX−9.0−11/2009

The Rx PDO contains the input data used to control the outputs (I/O.0 and I/O.1)
depending on the encoder value.

Byte

Assignment

0

Comparison value (LOW byte)

Bits 0 ... 7

Selection of comparison value

1

Comparison value (MID byte)

Bits 0 ... 7

2

Comparison value (HIGH byte)

Bits 0 ... 7

3

Reserved

4

Control

Bits 0 ... 1

Setpoint selection
00: No setpoint selection
01: Setpoint selection for output I/O.0
10: Setpoint selection for output I/O.1
11: Setpoint selection for outputs I/O.0 and I/O.1

Bit 2

Reserved

Bit 3

Condition for setting the output = HIGH
0: If SSI encoder value is higher than setpoint
1: If SSI encoder value is lower than setpoint

Bits 4 ... 7

Reserved

The Tx PDO contains the output data supplied by the encoder.

Byte

Assignment

0

SSI encoder value (LOW byte)

Bits 0 ... 7

Output of SSI encoder value

1

SSI encoder value (MID byte)

Bits 0 ... 7

2

SSI encoder value (HIGH byte)

Bits 0 ... 7

3

Reserved

4

Status

Bit 0

Status I/O.0

Bit 1

Status I/O.1

Bits 2 ... 7

Reserved

Input data

Output data

Advertising