1 system bus (can) / canopen, 1 before switching on, System bus (can) / canopen – Lenze EPM−T9XX Modular system User Manual

Page 285: Before switching on, Commissioning

Advertising
background image

System bus (CAN) / CANopen

Before switching on

11

Commissioning

11.1

11.1.1

L

11.1−1

EDSPM−TXXX−9.0−11/2009

11.1

System bus (CAN) / CANopen

11.1.1

Before switching on

Prior to supply voltage connection, check

l

the wiring for completeness, short circuits and earth faults

l

the wiring of the fieldbus

– A bus terminating resistor has to be connected to the first and the last

node.

l

spatial cable separation from signalling and mains cables.

)

Note!

After switching on the supply voltage, the modules of the I/O
system IP20 are initialised. During the initialisation, the modules
cannot be parameterised.

l

Initialisation time − modular system: approx. 10 s

l

Initialisation time − compact system: approx. 1 s