Networking via profibus−dp – Lenze EPM−T9XX Modular system User Manual

Page 272

Advertising
background image

Transmitting parameter data

Addressing with slot and index

10

Networking via PROFIBUS−DP

10.5

10.5.3

L

10.5−6

EDSPM−TXXX−9.0−11/2009

l

In the case of PROFIBUS Gateway, the 32 electronic modules can be
accessed via slot numbers 1 ... 32.

l

In the case of GatewayECO, the 8 electronic modules can be accessed via
slot numbers 1 ... 8.

Slot number

Index

Access

Description

1 ... 32

00

h

R

Read out diagnostic data record 0

W

Write parameters to the module

01

h

R

The corresponding diagnostic data record of the electronic module can be
read out via the index.

·

Example:

– Index 01

h

: read out diagnostic data record 1

– Index 02

h

: read out diagnostic data record 2

F1

h

R

Read out the module parameters

F2

h

R

Read out the process image of the module

R = read

W = write

Data of electronic modules