Parameterising 2/4xcounter module

Measuring the period (modes 17 and 19)

12

Parameter setting via system bus (CAN) / CANopen

12.4

12.4.10

L

12.4−27

EDSPM−TXXX−9.0−11/2009

Mode 17:

The output OUT 0 is set to HIGH level when the

measuring process starts, and is

set to LOW level, when the measuring process is completed. The output OUT1
indicates the output signal of OUT0 in an inverted way.

Mode 19:

The output OUT 0 is set to HIGH level when the

counting process starts, and is set

to LOW level, when the counting process is completed. The output OUT1 indicates
the output signal of OUT0 in an inverted way.

T

+

n

f

ref

@ m

T

Average period

f

ref

Reference frequency (see figure "counter access")

m

Content, counter 1 (number of reference frequency pulses)

n

Number of CLK pulses in counter 0 (corresponds to Compare unless prematurely
terminated by a HIGH signal at input IN4 (STOP)

epm−t092

Fig. 12.4−34

Counter access of the 2/4xcounter in the modes 17 and 19

OUT signal

Computing the period