The modular system, 4×analog input / output – Lenze EPM−T9XX Modular system User Manual

Page 95

Advertising
background image

4×analog input / output

4

The modular system

4.20

L

4.20−3

EDSPM−TXXX−9.0−11/2009

Type

4×analog input / output

Voltage supply

DC 5 V / 100 mA (via backplane bus)

External voltage supply

DC 24 V / 110 mA (DC 20.4 ... 28.8 V)

Short−circuit current

30 mA

Connectable cable cross−section

£ 2.5 mm

2

(

³ AWG 14)

Analog inputs

Number

2

Input area

Voltage

0 ... +10 V
−10 ... +10 V
+1 ... +5 V

Information on tolerances
can be found in the chapter
"Parameter setting"

Current

0 ... +20 mA
−20 ... +20 mA
+4 ... +20 mA

Conversion rate

[Hz]

3.7

7.5

15

30

60

123

168

202

Processing time per channel

[ms]

290

150

84

54

36

28

26

26

Resolution

[bit]

16

16

16

16

15

14

12

10

Electrical isolation from backplane bus

Yes, via optocouplers

Analog outputs

Number

2

Analog−to−digital converter

12 bits

Output ranges
(Tolerances refer to the upper limit of effective
range)

Voltage

0 ... +10 mA (±0.4 %)
−10 ... +10 mA (±0.2 %)
+1 ... +5 mA (±0.6 %)

Current

0 ... +20 mA (±0.6 %)
−20 ... +20 mA (±0.3 %)
+4 ... +20 mA (±0.8 %)

Actuator − input resistance

Voltage range

min. 1 k

W (output current max. 10 mA)

Current range

min. 500

W (output current max. 20 mA)

Delay time

10 ms

Electrical isolation from backplane bus

Yes, via optocouplers

Communication

Input data

4 bytes (one word per channel)

Output data

4 bytes

Parameter data

12 bytes

Diagnostic data

12 bytes

Dimensions

Width

25.4 mm

Height

76.0 mm

Depth

76.0 mm

Weight

100 g

Order number

EPM−T330

Technical data

Advertising