Diagnostics

Alarm messages

10

Networking via PROFIBUS−DP

10.6

10.6.3

L

10.6−7

EDSPM−TXXX−9.0−11/2009

)

Note!

Starting from byte 5, 16 bytes of additional alarm information are
added.

Bytes 5 to 8 correspond to the CPU diagnostic data record 0:

Byte

Assignment

Byte 5

Bit 0

1

Module error, an error was detected

Bit 1

1

Internal error in module

Bit 2

1

External error, module cannot be addressed

Bit 3

1

Channel error in the module

Bit4

1

No load voltage supply

Bit 5

1

No front connector

Bit 6

1

Module is not parameterised

Bit7

1

Parameter setting error

Byte 6

Bit 3 ... 0

Module class
1111

Digital module

0101

Analog module

1000

Counter module

Bit4

1

Channel information available

Bit 5

1

User information available

Bit 6

0

Reserved

Bit7

0

Reserved

Byte 7

Bit 7 ... 0

Reserved

Byte 8

Bit 7 ... 0

Reserved

Bytes 9 to 20 correspond to the CPU diagnostic data record 1:

Byte

Assignment

Byte 9

Bit 7 ... 0

01110000

Digital module with inputs

01110001

Analog module with inputs

01110010

Digital module with outputs

01110011

Analog module with outputs

01110100

Analog module with inputs and outputs

01110101

Counter module

Byte 10

Bit 7 ... 0

Length of the channel−specific diagnostics

Byte 11

Bit 7 ... 0

Number of channels per module

Byte 12

Bit 7 ... 0

Position (channel) of the diagnostic event

Byte 13

Bit 7 ... 0

Diagnostic event for channel/channel group 0 (see module description)

...

...

...

Byte 19

Bit 7 ... 0

Diagnostic event for channel/channel group 7 (see module description)