16×digital input

4

The modular system

4.6

L

4.6−2

EDSPM−TXXX−9.0−11/2009

DI 16xDC24V

EPM – T211

1

2

.0

3

.1

4

.2

5

.3

6

.4

7

.5

8

.6

9

.7

10

.0

11

.1

12

.2

13

.3

14

.4

15

.5

16

.6

17

.7

18

0

1

+

1

2

3

4

14

15

16

17

18

DC 24 V (DC 18 … 28.8 V)

.

epm−t125

epm−t121

Fig. 4.6−2

Front view and connection of 16×digital input

0

2 × status display .0 ... .7; LED
(green) is lit when a HIGH level is
recognised

1

Terminal strip assignment details

1

Not assigned

2

Digital input E.0

3

Digital input E.1

4

Digital input E.2

...

...

14

Digital input E.12

15

Digital input E.13

16

Digital input E.14

17

Digital input E.15

18

GND (reference potential)

.

Connection to backplane bus

Type

16×digital input

Voltage supply

DC 5 V / 30 mA (via backplane bus)

Connectable cable cross−section

£ 1.5 mm

2

(

³ AWG 16)

Digital inputs

Rated input voltage

DC 24 V (DC 18 ... 28.8 V)

Number of inputs

16

Level

LOW: DC 0 ... 5 V
HIGH: DC 15 ... 30 V

Input resistance

3.3 k

W

Delay time

3 ms

Electrical isolation from backplane bus

Yes, via optocouplers

Communication

Input data

2 bytes

Dimensions

Width

25.4 mm

Height

76.0 mm

Depth

76.0 mm

Weight

50 g

Order designation

EPM−T211

Status display and terminal
assignment

Technical data