Parameterising SSI interface

Input data / output data

13

Parameter setting via PROFIBUS−DP

13.3

13.3.2

L

13.3−3

EDSPM−TXXX−9.0−11/2009

13.3.2

Input data / output data

L

X1

PW

ER

RD

DE

DC
24V

+

-

EPM – T120 xx.xx

A
D
R.

64
32
16
8
4
2
1

1

0

Data to module

Control

Dat

a

In

HB

D

a

taI

nM

B

D

a

taI

nL

B

S

tatus

Dat

a

Out

HB

Dat

a

Out

MB

Dat

a

Out

LB

0

E/A.1

E/A.0

SSI

Encoder

0

1

1

2

2

3

3

Data from module

Gateway

SSI-Interface

.0

.1

.2

.3

.4

.5

.6

.7

1

2

3

4

5

6

7

8

9

L

10

+24 V

Hold

E/A.0

epm−t250

Fig. 13.3−1

Data input /output of SSI interface

For the data input / data output, 4 bytes are available which are transmitted to the
module or output by the module.

)

Note!

Input and output data are lost when the supply voltage is
disconnected; they are not saved!

The input data can be used to control the outputs (I/O.0 and I/O.1) depending on
the encoder value.

Byte

Assignment

0

Control

Bits 0 ... 1
%

Setpoint selection
00: No setpoint selection
01: Setpoint selection for output I/O.0
10: Setpoint selection for output I/O.1
11: Setpoint selection for outputs I/O.0 and I/O.1

Bit 2

Reserved

Bit 3

Condition for setting the output = HIGH
0: If SSI encoder value is higher than setpoint
1: If SSI encoder value is lower than setpoint

Bits 4 ... 7

Reserved

1

Comparison value (HIGH byte)

Bits 0 ... 7

Selection of comparison value

2

Comparison value (MID byte)

Bits 0 ... 7

3

Comparison value (LOW byte)

Bits 0 ... 7

Byte

Assignment

0

Status

Bit 0

Status I/O.0

Bit 1

Status I/O.1

Bits 2 ... 7
%

Reserved

1

SSI encoder value (HIGH byte)

Bits 0 ... 7

Output of SSI encoder value

2

SSI encoder value (MID byte)

Bits 0 ... 7

3

SSI encoder value (LOW byte)

Bits 0 ... 7

Input data

Output data