Network via canopen, Heartbeat – Lenze EPM−T9XX Modular system User Manual

Page 242

Advertising
background image

Heartbeat

9

Network via CANopen

9.7

L

9.7−2

EDSPM−TXXX−9.0−11/2009

11 bits

1 byte of user data

Identifier

Device status (bits 0 ... 6)

bits 7

1792

d

(700

h

)

reserved

Identifier:

Formula

Information

Identifier

= Basic identifier + node address
= 1792

d

+ xx

The basic identifiers for heartbeat is firmly
adjusted to 1792

d

(700

h

)

xx = node address of the I/O system IP20

Device status (bit 1 ... 6) of the heartbeat producer:

Command

(hex)

Status

00

Boot−up

05

Operational

04

Stopped

7F

Pre−Operational

Indices for setting

Index

Name

Possible settings

Important

Lenze

Selection

I1016

h

¿

Heartbeat
consumer time

Data contents

I/O system IP20 can monitor up to five
nodes (subindex 1 ... 5).
If the monitored node does not respond, I/O
system IP20 changes to the status
"Pre−Operational". The outputs switch to a
defined state.

^ 9.7−1

Heartbeat time

Node ID

Reserved

Byte 0

Byte 1

Byte 2

Byte 3

00

h

00

h

00

h

00

h

1 Heartbeat time

0

0

{1 ms}

65535

·

In the compact system, only subindex 1
is available

·

Heartbeat time:

– The monitored node must respond

within the time set. The time is set in
byte 0 and 1.

– If the monitored node does not

respond within the set time, I/O
system IP20 switches to the
communication status set under
I1029

h

– The communication status is reset

when a new heartbeat telegram is
received

·

Node ID:

– Node address of the node to be

monitored. The address is set in
byte 2.

Node ID

0

0

{1}

255

2 Heartbeat time

0

0

{1 ms}

65535

Node ID

0

0

{1}

255

3 Heartbeat time

0

0

{1 ms}

65535

Node ID

0

0

{1}

255

4 Heartbeat time

0

0

{1 ms}

65535

Node ID

0

0

{1}

255

5 Heartbeat time

0

0

{1 ms}

65535

Node ID

0

0

{1}

255

I1017

h

¿

Heartbeat producer
time

0

0

{1 ms}

65535 I/O system IP20 can be monitored by other

nodes.
Within this time the device status of I/O
system IP20 is transmitted to the fieldbus.
Not available for system bus (CAN)
communication protocol

^ 9.7−1

0

Function is not active

)

Note!

The Lenze 9300 servo PLC and Drive PLC in connection with the
function library LenzeCanDSxDrv.lib support the "heartbeat"
function.

Status telegram