13 parameter setting via profibus−dp – Lenze EPM−T9XX Modular system User Manual

Page 420

Advertising
background image

Parameterising analog modules

Signal functions of 4xanalog input

13

Parameter setting via PROFIBUS−DP

13.1

13.1.4

L

13.1−8

EDSPM−TXXX−9.0−11/2009

Paramete
r bytes
2/3/4/5

Tolerance

2)

Format

1)

Signal range

Signal function

18

h

Temperature
measurement with
thermoelement and
internal
compensation 5

)

Type J

−210.0

{0.1 °C}

+850.0

S7

Two’s

complement

±1.5 °C

19

h

Type K

−270.0

{0.1 °C}

+1200.0

±2 °C

1A

h

Type N

−200.0

{0.1 °C}

+1300.0

±2 °C

1Bh

Type R

−50.0

{0.1 °C}

+1760.0

±5 °C

1C

h

Type T

−270.0

{0.1 °C}

+400.0

±2 °C

1D

h

Type S

−50.0

{0.1 °C}

+1760.0

±5 °C

27

h

Voltage
measurement

0 ... 50
mV

0.00
0

{0.01 mV}

{1

dec

}

+50.00

27648

S7

Two’s

complement

±0.1 % of the
final value

Min.

Limit

values

Max.

0.00
0

+59.25 mV

32767

dec

28

h

Voltage
measurement

±10 V

−10.00
−27648

{0.01V}

{1

dec

}

+10.00

27648

S7

Two’s

complement

±0.05 % of
the final value

Min.

Limit

values

Max.

−11.85 V
−32767

dec

+11.85 V

32767

dec

29

h

Voltage
measurement

±4 V

−4.00
−27648

{0.01V}

{1

dec

}

+4.00 V

27648

dec

S7

Two’s

complement

±0.05 % of
the final value

Min.

Limit

values

Max.

−4.74 V
−32767

dec

+4.74 V

32767

dec

2A

h

Voltage
measurement

±400 mV

−400
−27648

{1 mV}

{1

dec

}

+400

27648

S7

Two’s

complement

±0.1 % of the
final value

Min.

Limit

values

Max.

−474 mV
−32767

dec

+474 mV

32767

dec

2Bh

Voltage
measurement

±10 V

−10.00
−16384

{0.01V}

{1

dec

}

+10.00

16384

S5

Sum and sign

±0.2 % of the
final value

Min.

Limit

values

Max.

−12.50 V
−20480

dec

+12.50 V
20480

dec

2C

h

Current
measurement

±20 mA

−20.00
−27648

{0.01 mA}

{1

dec

}

+20.00

27648

S7

Two’s

complement

±0.05 % of
the final value

Min.

Limit

values

Max.

−23.70 mA
−32767

dec

+23.70 mA

+32767

dec

2D

h

Current
measurement

4 ... 20
mA

4.00
0

{0.01 mA}

{1

dec

}

20.00

27648

S7

Two’s

complement

±0.05 % of
the final value

Min.

Limit

values

Max.

0 mA
−5530

dec

+22.96 mA

+32767

dec

2E

h

Current
measurement

4 ... 20
mA

4.00
0

{0.01 mA}

{1

dec

}

20.00

16384

S5

Sum and sign

±0.2 % of the
final value

Min.

Limit

values

Max.

0 mA
−4096

dec

+22.96 mA

+20480

dec

Advertising